The B112LP is a 4-wire base with Form A&C relay contacts, for use with 100 Series smoke detectors.
UPC: 783863002892
Also known as: BK-B112LP
Technical Specifications:
- Start-up Time: 34.0 seconds maximum
- Reset Voltage: 1.4 VDC minimum
- Alarm Ratings: 17 - 36 mA
- Standby Range: 20 - 29 VDC
- Start-up Capacitance: 0.02uF maximum
- Maximum Ripple VoltagE: 4 Volts peak-to-peak
- System Voltage: 24VDC
- Operating Temperature: 0C to 49C (32F to 120F)
- Mounting: 4" square box with or without plaster ring. Min. depth 1.5"
- Base Heighrt: 0.95" (24mm)
- Base diameter: 6.2" (157mm)
- Operating Humidity Range: 10 to 93 percent relative humidity, non-condensing
- Weight: 0.3lb
|