Macurco CD-6 Carbon Dioxide Detector, Controller and Transducer

  • MPN: CD-6
  • JMAC ID: 200599918
$584.00
+ Free Shipping
JMAC_ID:
200599918
df_manual_boost:
1.75
The Macurco CD-6 is a low voltage, dual relay Carbon Dioxide (CO2) detector, controller and transducer. The CD-6 has selectable 4-20 mA output, buzzer and digital display options. It is an electronic detection system used to measure the concentration of Carbon Dioxide and provide feedback and automatic ventilation control to help reduce CO2 concentrations in conference rooms, classrooms, meeting halls or similar applications. The CD-6 is a low level meter capable of displaying from 0-2000 ppm (parts per million) of Carbon dioxide. The CD-6 is factory calibrated and 100% tested for proper operation. The CD-6 uses an automated background calibration program to set the clean air level on a regular basis.

UPC: 783748834808
Also known as: CD6

Technical Specifications:
  • Operating Environment: 32°F to 122° F (0C to 50C), 10 to 90% RH non-condensing
  • Digital display: 4 digit LED selectable to off or on (default).
  • Buzzer: 85 dBA at 10cm settable to off or on (default)
  • Current Loop, 4-20 mA for 0-2000 ppm CO2, selectable to off or on (default)
  • Alarm relay settings: “dIS”(disabled), 900, 1000... to 2000 ppm (default)
  • Alarm relay actuation: selectable N.O. (default) or N.C.
  • Alarm relay: 0.5A 120 V, 60 VA
  • Fan relay latching or not latching (default) selectable
  • Fan Relay Minimum Runtime settings are 0 (default), 3, 5, 10 or 15 minutes
  • Fan Delay Settings of 0, 1, 3 (default), 5 and 10 minutes
  • Fan relay actuation: selectable at dIS (disabled), 600, 700, 800, 900, 1000 (default), 1100, 1200, 1300, 1400, 1500 ppm
  • Fan relay: 5 A, 240 VAC, pilot duty, SPDT, latching or non-latching
  • Mounting box: (not included) 4x4 electric
  • Connections: plugs/terminals
  • Color: White or dark gray
  • Size: 4 1/2 x 4 x 2 1/8 in. (11.4 X 11.4 X 5.3 cm)
  • Shipping Weight: 1 pound (0.45 kg)
  • Current (max) @ 24 VDC: 126 mA in alarm (two relays), 108 mA (fan relay only) and 85 mA (standby)
  • Power: 3 W (max) from 12 to 24 VAC or 12 to 32 VDC


For more information about the Macurco CD-6, please contact us.
  • Low level meter capable of displaying from 0-2000 ppm of CO2
  • Calibration verification test kit is available. One screw allows access for gas test
  • Supervised system: any internal detector problem will cause the fan & alarm relay to activate
  • CD-6 mounts on a standard 4x4 electrical box and becomes cover for the box
  • 4-20 mA Current Loop
  • 0.5 A N.O. or N.C. alarm relay connects to warning devices or control panels
  • Selectable fan and alarm relay activation
  • ETL LISTED Certified to CAN/CSA Std. C22.2 No 61010-1 Conforms to UL Std. 61010-1
  • The CD-6 uses an automated background calibration program to set the clean air level on a regular basis
  • 5 A SPDT fan relay controls starters of ventilations

1 Review

  • 5
    MACURCO-CD-6

    Posted by 147735 on Oct 13th 2019