Macurco RD-12-WHITE Refrigerants Gas Detector, White Housing

  • MPN: RD-12 WHITE
  • JMAC ID: 200599934
$480.75
+ Free Shipping
JMAC_ID:
200599934
df_manual_boost:
1.50
The Macurco 12-Series are line voltage powered (100-240VAC), dual relay gas detector, controller and transducers. The 12-Series utilizes an internal switching power supply that is capable of using line voltage between 100 and 240VAC and 50-60Hz. The 12-Series have selectable 4-20mA output, buzzer and digital display options. It is an electronic detection system used to measure the concentration of various gases and provide feedback and automatic control to help reduce gas concentrations in parking garages, maintenance facilities or other commercial applications.


Also known as: RD12WHITE

Technical Specifications:
  • Alarm relay: 0.5A 120 V, 60 VA
  • Operating altitude: Up to 5,000m (16,404ft)
  • Operating Environment: 0°F to 125°F (-18ï‚°C to 52ï‚°C).10 to 90% RH non-condensing
  • Digital display: 3 digit LED selectable to on (default) or off
  • Buzzer: 85 dBA at 10cm settable to on (default) or off
  • Current Loop, 4-20 mA for 0-1,000 ppm refrigerant gas, selectable to off or on (default)
  • Alarm relay settings: diS, 100, 125, 150, 200, 300 (default), 400, 500 or 600ppm
  • Alarm relay actuation: selectable N.O. default or N.C.
  • Fan relay latching or not latching (default) selectable
  • Fan Minimum Runtime settings are 0 (default), 3, 5, 10 or 15 minutes
  • Fan Delay Settings of 0, 1, 3 (default), 5 and 10 minutes
  • Fan relay actuation: selectable at diS (disable), OFF, 100 (default), 150, 200, 250, 300, 350ppm
  • Fan relay: 5 A, 240 VAC, pilot duty, SPDT, latching or non-latching
  • Mounting box: (not included) 4x4 electric
  • Connections: plugs/terminals
  • Color: White
  • Size: 4 1/2 x 4 x 2 1/8 in. (11.4 X 11.4 X 5.3 cm)
  • Shipping Weight: 1 pound (0.45 kg)
  • Current: 1.0 A MAX
  • Power: 100-240VAC (50 TO 60 HZ)


For more information about the Macurco RD-12 WHITE, please contact us.
  • Supervised system: any internal detector problem will cause the fan & Alarm relay to activate
  • 4-20 mA Current Loop
  • 0.5 A N.O. or N.C. alarm relay connects to warning devices or control panels
  • 5 A SPDT fan relay controls starters of exhaust fans
  • Selectable fan and alarm relay activation
  • Low level meter capable of displaying from 0-1,000 ppm of refrigerant gas
  • ETL Listed to UL 61010-1 and CAN/CSA C22.2 No 61010-1
  • White housing
  • RD-12 mounts on a standard 4x4 electrical box and becomes cover for the box
Live Chat