Macurco DVP-120M Addressable Detection and Ventilation Panel
-
MPN: DVP-120M
-
JMAC ID: 200470830
The Macurco DVP-120M is a gas detection and ventilation control panel supporting 12 analog inputs and up to 87 digital detectors. It provides 3 configurable ventilation zones, 3 SPDT fan/alarm relays, 3 RS-485 digital channels, a backlit LCD, and external horn and strobe drivers. The panel works with compatible Macurco gas detectors to control ventilation and alarm functions in commercial gas monitoring applications.
Macurco DVP-120M Gas Detection and Ventilation Control Panel
The Macurco DVP-120M is a centralized gas detection and exhaust ventilation controller designed for commercial applications that require automatic response to monitored gas concentrations. The panel provides 12 analog 4-20 mA input channels plus 3 RS-485 channels supporting up to 87 digital detectors, with as many as 29 addressable detectors connected to each RS-485 channel. This hybrid architecture supports both analog and digital Macurco detector installations from a single control panel.
The DVP-120M supports up to 3 independently configurable ventilation control zones. Each zone can respond to gas concentration levels from one or more connected detectors and can also operate according to time-of-day settings. Three onboard SPDT relays are rated for 10 A resistive loads at up to 240 VAC and can be configured for exhaust fan control or alarm signaling. Relay activation delays and minimum run times are adjustable from 0 to 15 minutes in 1-second increments.
The control panel includes a 2-line, 16-character backlit LCD with an external keypad for system status, detector readings, relay status, and password-protected configuration. Six front-panel LEDs indicate power, alarm or warning conditions, hush status, and the state of each of the 3 relays. An internal buzzer produces approximately 90 dBA at 1 ft, while 2 external 24 VDC drivers rated at up to 250 mA each support compatible horn and strobe notification devices.
The Macurco DVP-120M operates from 90-250 VAC, 47-63 Hz single-phase power and is housed in a lockable NEMA 1 enclosure measuring approximately 10.5 x 12.5 x 2 inches. The panel operates from 32 F to 104 F (0 C to 40 C) at 0% to 95% non-condensing relative humidity. It is compatible with Macurco 6-Series and 12-Series gas detectors and is ETL Listed, including listing to UL 508A and CAN/CSA-C22.2 No. 14 requirements documented for the DVP-120M platform.
UPC: 783748833207
Also known as: DVP120M
Technical Specifications:
|
For more information about the Macurco DVP-120M, please contact us.
- Up to three ventilation control zones can be defined
- ETL Listed to UL 508A, CAN/CSA-C22.2 No. 14-13
- Each zone can be controlled based on transducer signals and/or time of day
- External keypad for user selection of the transducer/alarm display and setting the configuration
- Externally visible LCD display showing the status of each transducer and relay
- Three RS-485 digital input channels - 29 addressable sensors per channel
- Externally visible system, alarm and relay status indicators
- Compatible with all Macurco 6-Series gas detectors and MRS-485 adapter
- Twelve analog (current loop) input channels
- Three 10A, 240 VAC SPDT fan/alarm relays
- Drivers for external Horn and Strobe
- Fail safe operation can be implemented
- Lockable NEMA 1 type enclosure
- Modular input and output connectors