Ditek DTK-KG2 Kool Guard Series Intelligent Voltage Monitoring
-
MPN: DTK-KG2
-
JMAC ID: 202492852
The DITEK DTK-KG2 Kool Guard 2 is an intelligent HVAC voltage monitor and surge protection device designed for 120/240VAC and 120/208VAC split-phase systems with equipment ratings up to 40A MCA. It protects mini-splits, inverter-driven compressors, and condensing units against damaging voltage fluctuations and transient surges. Featuring 104V undervoltage and 130V overvoltage thresholds, 50,000A surge protection, and a programmable restart delay, the DTK-KG2 automatically disconnects equipment during unsafe voltage conditions and restores power after recovery.
DITEK DTK-KG2 Kool Guard 2 Intelligent HVAC Voltage Monitor and Surge Protector
The DITEK DTK-KG2 Kool Guard 2 combines intelligent voltage monitoring, automatic equipment disconnection, and transient surge protection to safeguard sensitive HVAC electronics and mechanical components. Designed for 120/240VAC and 120/208VAC split-phase electrical systems, the device is compatible with equipment rated up to 40A minimum circuit ampacity (MCA). It monitors both electrical phases independently to detect harmful voltage fluctuations that can affect compressor operation, control boards, and other electrical components. With a 50,000A surge current rating, the DTK-KG2 also incorporates surge protection components to divert transient voltage spikes away from connected equipment. Typical applications include ductless mini-split systems, inverter-driven HVAC equipment, and outdoor condensing units.
The DTK-KG2 provides undervoltage protection at 104VAC and overvoltage protection at 130VAC, measured line-to-ground on each phase. Its voltage monitoring circuitry evaluates each complete 60Hz power cycle, providing a 1/60-second detection interval for abnormal voltage conditions. When either phase falls outside the programmed operating range, the device disconnects power to the protected equipment. Once voltage returns to acceptable levels, an integrated 3-minute short-cycle delay prevents immediate equipment restart, helping protect compressors against rapid cycling. Installers can alternatively select a 30-second delay through an internal jumper. Dual red and green LED indicators identify normal operation, undervoltage, overvoltage, recovery delays, and service conditions, allowing technicians to diagnose electrical problems directly at the unit.
The DITEK DTK-KG2 features a UL Type 4X polycarbonate enclosure designed for indoor or outdoor installation near HVAC disconnects and condensing equipment. Measuring 6.25 inches long, 6.25 inches wide, and 2.62 inches deep, the enclosure supports series-wired installation between the electrical disconnect and protected equipment. Mechanical terminals accommodate 14-6 AWG stranded copper conductors, while conduit connections support 1/2-inch or 3/4-inch NPT fittings. The enclosure includes integrated mounting tabs and separate line-input and equipment-output connections to simplify installation and maintain proper circuit separation. Installation must follow the manufacturer's wiring instructions and applicable electrical codes. The DTK-KG2 is certified to UL 60947-1, UL 60947-5-1, and applicable CSA standards, with RoHS compliance.
For ongoing HVAC protection, the DTK-KG2 continuously monitors incoming voltage and provides diagnostic LED feedback to distinguish power quality problems from normal equipment operation. A service-required indication identifies expired surge protection components and signals that the unit requires replacement. Compatible units also include a Generator Mode for standby or backup generator operation, which maintains surge protection while temporarily disabling voltage monitoring to prevent interruptions associated with generator power. Normal voltage monitoring must be restored when returning to utility power. The device's integrated voltage monitoring, automatic power interruption, restart delay, and surge suppression provide a consolidated protective solution for residential and commercial HVAC installations. DITEK backs the DTK-KG2 with a 10-year limited warranty, subject to the manufacturer's warranty terms and installation requirements.
UPC: 782980521385
Also known as: DK-KG2, DTK-DTKKG2, DTKKG2
For more information about the Ditek DTK-KG2, please contact us.
- Auto-calibration feature eliminates the need to manually calibrate the unit to the specific input voltage
- Protection for undervoltage & overvoltage events on 120/240VAC or 120/208VAC split phase circuits up to 40A
- Safely disconnects power to the system for 3 minutes allowing input voltage to return to normal range
- Ideal protection for inverter-driven compressor systems and mini-splits
- Diagnostic red and green LEDs indicate exactly what voltage condition is present
- Surge protection components included to divert harmful transient voltages away from the equipment
- Accepts either 1/2" or 3/4" NPT flexible conduit
- UL Listed