Conventional Accessories
Conventional Panel Expanders & Modules
These modules add circuits, relays, and communication to Potter conventional fire alarm control panels.
The IDC-6 initiating device circuit expander provides 6 additional inputs per module, and up to 31 IDC-6 modules are supported. Its circuits are power-limited and supervised, suitable to monitor 2-wire smoke detectors or for automatic, manual, waterflow, or supervisory service, and it communicates over the P-Link bus; the CA-4064 is a Class A expander for the PFC-4064. For the PFC-5004E, the ZA-42 zone adder expands the panel to eight Class B zones or four Class A zones with four notification circuits rated at 1.7 amps each, and the ARM-4 provides 4 relays to PFC-5000 series panels. For monitoring, the UDACT-9100 lets PFC-5000 or PFC-9000 series panels transmit alarm, supervisory, and trouble information on two telephone lines and can be configured for DACT or UDACT operation, and it can be set up locally with its on-board keypad and the CFG-LCD UDACT programming tool.
See the panels these serve under conventional panels and releasing accessories, or all fire products. Browse the full Potter catalog. Contact our team for panel compatibility.