Gentex STRR (917-0072-002) Single/Multiple Station Smoke Alarm, Integral Heat Thermal
-
MPN: STRR (917-0072-002)
-
JMAC ID: 202790798
The Gentex STRR (917-0072-002) is a 120 VAC multi-criteria photoelectric smoke and heat alarm with an integral 135 F rate-of-rise thermal sensor, two sets of Form A/Form C relay contacts, and 9V battery backup. Part of the Gentex S Series, it features an 85 dBA temporal-3 evacuation horn, tandem interconnection with compatible Gentex alarms, programmable relay operation, and a 10-year end-of-life indicator. The STRR is listed to ANSI/UL 217, 9th Edition, and provides combined smoke and heat detection for residential and institutional occupancies.
Gentex STRR 120VAC Photoelectric Smoke and Heat Alarm with Dual Relays
The Gentex STRR (917-0072-002) is a hardwired, multi-criteria smoke and heat alarm designed to detect smoke and elevated temperatures while providing local audible evacuation signaling. Part of the Gentex S Series, this combination alarm integrates photoelectric light-scattering smoke sensing and a self-restoring 135 F fixed-temperature/rate-of-rise thermal sensor within a single white housing. The STRR is designed for single-station and multiple-station applications in residential and institutional occupancies, including homes, apartments, hotels, motels, and qualifying healthcare facilities. Its multi-criteria sensing technology helps distinguish fire conditions from common sources of nuisance alarms, while the integrated thermal sensor provides an additional means of detecting elevated temperatures. The alarm incorporates two sets of auxiliary relay contacts for integration with compatible remote annunciation and building control equipment.
The STRR operates on 120 VAC, 60 Hz primary power with a 9V alkaline battery backup that maintains alarm functionality during an interruption of building power. Its rated operating current is 0.055 amps at 120 VAC, and its photoelectric sensing chamber provides a nominal smoke sensitivity of 2.5% obscuration. The integrated piezoelectric horn produces an 85 dBA audible alarm at 10 feet with a nominal frequency of 3,100 Hz, using the temporal-3 evacuation pattern for smoke and heat alarm conditions. The device includes two sets of Form A and Form C relay contacts for smoke and heat-related auxiliary signaling, allowing compatible external equipment to respond to alarm conditions. Relay operation is programmable, and the contacts remain functional during battery backup operation. Additional capabilities include an eight-hour alarm memory, push-button self-testing, functional testing, and automatic restoration after the detected alarm condition clears.
The Gentex STRR supports tandem interconnection with compatible Gentex smoke, heat, carbon monoxide, and combination smoke/CO alarms using the manufacturer's DUALINK technology. When an interconnected smoke or heat alarm activates, compatible connected devices produce the temporal-3 smoke evacuation warning, while a connected carbon monoxide alarm can initiate the appropriate temporal-4 warning pattern across supported interconnected alarms. The system supports up to 18 interconnected initiating devices, including a maximum of 12 S Series or SC Series smoke alarms, subject to the manufacturer's wiring requirements. The STRR includes a quick-disconnect wiring harness, front-loading battery drawer, and mounting hardware compatible with standard electrical junction boxes. Its circular housing measures approximately 5.5 inches in diameter and 1.75 inches deep, providing a compact ceiling- or wall-mounted installation. A fully insect-screened sensing chamber, pulsing status LEDs, and low- or missing-battery indicators support routine inspection and maintenance.
The Gentex STRR is designed for residential and institutional fire warning applications requiring combined photoelectric smoke detection, integral thermal sensing, battery backup, and auxiliary relay signaling. Its smoke alarm functionality is listed to ANSI/UL 217, 9th Edition, and the S Series is designed for installations subject to applicable NFPA 72 and building fire safety requirements. The STRR features a 10-year end-of-life indicator that alerts occupants when the alarm reaches its designated replacement age, while the manufacturer recommends weekly testing to verify operation. A green LED indicates the presence of AC power, and a red LED provides sensing and alarm status information. Unlike the Gentex SR model, which provides smoke detection and one set of relay contacts, the STRR adds integral 135 F thermal detection and two sets of auxiliary relay contacts. The STRR also differs from the SHRR, which uses an isolated thermal sensor configuration. With its 120 VAC operation, 9V battery backup, interconnected alarm communication, and combined smoke and heat sensing, the Gentex STRR provides a versatile fire warning solution for compatible residential and institutional installations. The product carries a one-year manufacturer warranty from the date of purchase.
UPC: 700217047019
For more information about the Gentex STRR (917-0072-002), please contact us.
- Listed to UL 217, 9th Edition
- 10-year end-of-life indicator
- Temporal 3 evacuation signal pattern for smoke and heat annunciation
- 85 dBA evacuation horn piezo
- Horn frequency 3100Hz
- Programmable relay operation
- Relays operate on battery back-up
- Push button self-test