GENTEX SCRR (918-0033-002)
-
MPN: SCRR (918-0033-002)
-
JMAC ID: 202790807
Overview
The Gentex SCRR-918-0033-002 combines multi-criteria photoelectric smoke and electrochemical CO sensing in a 120 VAC hard-wired unit with 9 V alkaline battery backup, and features two independent sets of Form A/Form C relay contacts for enhanced system integration. This model is well suited for demanding fire-alarm system environments in commercial, institutional or multi-unit settings.
With its advanced sensing, dual relay capability and robust performance, the SCRR model supports comprehensive life-safety monitoring while keeping nuisance alarms to a minimum.
Technical Specifications
This alarm operates on 120V AC power with a 9V battery backup, ensuring it functions even during power failures. Key features include an 85 dBA alarm horn, dual detection for smoke and CO, and compliance with UL 217 and UL 2034 standards. The advanced smoke detection system minimizes nuisance alarms while still providing immediate alerts when needed, making it a reliable choice for various environments.
Application Areas
The SCRR-918-0033-002 is perfect for versatile installations across various applications, including single-family homes, apartments, hospitals, and hotels. Its sleek, compact design allows for easy integration into existing systems, providing seamless monitoring and safety assurance for residents and staff alike. Whether in new constructions or retrofits, this model enhances safety standards and meets modern regulations.
Competitive Edge
Compared to similar products from competitors like Kidde and First Alert, the Gentex SCRR demonstrates superior reliability due to its advanced sensor technology and robust alarm settings. These advantages position it as an ideal choice for both safety professionals and end-users looking for dependable smoke and CO detection solutions.
UPC: 700217047156
Technical Specifications:
|
For more information about the Gentex SCRR (918-0033-002), please contact us.
- Self-Test Functions: Incorporates push-button self-test to verify proper operation.
- Alarm Memory: Keeps track of recent alarm events with an 8-hour memory function.
- Audible Alerts: Emits an 85 dBA alarm with a distinct sound pattern to ensure clear notifications.
- Dual Detection: Utilizes photoelectric light scattering technology for smoke detection and an electrochemical sensor for CO detection, providing comprehensive monitoring.
- Battery Backup: Ensures operation during power outages with a 9V alkaline battery.
- Relay Outputs: Features two sets of Form A/Form C contacts for easy integration with auxiliary devices.
- Compliance Assurance: Listed to UL 217 and UL 2034 safety standards for reliability.
- Interconnectivity: Can connect with up to 12 other Gentex alarms for expanded coverage.
- Design: Combination smoke and carbon monoxide alarm with dual relay outputs.
- Operation: Multi-criteria photoelectric smoke sensor plus electrochemical CO sensor.
- Relay Output: Two sets of Form A/Form C relay contacts for independent control functions.
- Alarm Pattern: Temporal 3 (smoke) and Temporal 4 (CO) audible patterns.
- Indicator: Visual LED indicators show alarm, power, and trouble status.
- Mounting: Compact, surface-mount base simplifies installation.
- Application: Designed for use in multi-unit residential, commercial, and healthcare facilities.