EtherWAN SDR-120-48 120W/2.5A DIN-Rail 48VDC Industrial Power Supply

  • MPN: SDR-120-48
  • JMAC ID: 200412195
$238.12
JMAC_ID:
200412195
df_manual_boost:
1.75
The EtherWAN SDR-120-48 is a 120W/2.5A DIN-rail 48VDC industrial power supply.

UPC: 084765300105
Also known as: ET-SDR12048, SDR12048

Technical Specifications:
  • Storage Humidity: 10% to 95% RH
  • Working Humidity: 20% to 95% RH non-condensing
  • Storage Temperature: -40°C to 85°C (-40°F to 185°F), 10 to 95% RH
  • Operating Temperature: -25°C to 70°C (-13°F to 158°F); Refers to output load derating curve
  • Protection type: Shut down o/p voltage, recovers automatically after temperature goes down
  • Over Temperature Protection: 95°C ± 5°C (TSW: detected on heatsink of power switch)
  • Over Load Protection: Normally works within 110 to 150% rated output power for more than 3 seconds and then shut down o/p voltage; >150% rated power, constant current limiting with autorecovery within 3 seconds and shut down o/p voltage after 3 seconds
  • Protection type : Shut down o/p voltage, re-power on to recover
  • Over Voltage Protection: 56 to 65V
  • Installation: DIN-Rail
  • Weight: 0.67kg
  • Dimensions: 40mm (W) x 113.5mm (D) x 125.2mm (H) (1.6” (W) x 4.46” (D) x 4.93” (H))
  • Casing: Aluminum case
  • Hold up Time: 20ms/230VAC, 20ms/115VAC at full load
  • Setup, Rise Time: 1500ms, 60ms/230VAC, 3000ms, 60ms/115VAC at full load
  • Load Regulation: ± 1.0%
  • Line Regulation: ± 0.5%
  • Voltage Tolerance: ± 1.0%
  • Voltage Adj. Range: 48 to 55V
  • Ripple & Noise (max.): 120mVp-p
  • Peak Current: 3.75A
  • Rated Power: 120W
  • Current Range: 0 to 2.5A
  • Rated Current: 2.5A
  • DC Voltage: 48V
  • Leakage Current: <1mA / 240VAC
  • Inrush Current (Typ.): 35A/115VAC, 70A/230VAC
  • AC Current (Typ.): 1.4A/115VAC, 0.7A/230VAC
  • Efficiency: 90.5%
  • Frequency Range: 47 to 63Hz
  • Voltage Range: full load 88 to 264VAC, 124 to 370VDC


For more information about the EtherWAN SDR-120-48, please contact us.
  • High efficiency 90.5% and low power dissipation
  • -25°C to 70°C operating temperature range
  • Protections: Short circuit / Over load / Over voltage / Over temperature
  • Can be installed o DIN-rail TS-35 / 7.5 or 15
  • UL508 (Industrial control equipment) approved
Live Chat